High Pressure Boilers
|
|
Type NCB
|
| Natural Circulation Boiler upto 100 bar operation pressure |
High Pressure Natural
Circulation
Boilers
NCB
are applicable for high temperature heating
processes,
especially in Vegetable Oil Industry.
In comparison to thermal oil heaters, contamination
of the heated medium in case of
leakage is impossible
with the NCB-system.
|
Typical Fields of Application
- Food Industry
e. g. for edible
oil desodorizers and
for the fabrication of magerine and fats.
|
| |
 |
Features of the NCB boiler
- high efficiency on the optimized convection surface.
- no bushings in the tube system. This provides
safe natural circulation in every
operating status.
- tube system is mounted stress-free and gas tight.
- transport of NCB can be effected for smaller types in standard containers-even
the largest standard model.
The NCB is a natural circulation steam generator
at which the heat consumers are
connected through a closed steam-condensate system.
Therefore the heat consumers
have to be located above the NCB with a slight
lateral move. By this a steam-condensate
system will be built, at which the condensate flows to the NCB with particular
slope.
The connecting steam
and condensation piping forms part of the
hermetic system and
therefore design and selection of materials
must be in accordance with
the regulations for steam boilers.
The design of the mountings, fittings
and the safety valve
is also vacuum tight.
Because
of the sealed system there's no risk of corrosion by ambient air entering the
system.
This means less costs for maintenance.
Due to the absolute pressure and vacuum tight system the NCB has to be filled
with special
feedwater only once - operation is guaranteed
for months and years without refilling.
The Natural
Circulation
Boiler
NCB is designed as 3
pass boiler in vertical design. The
heating surface consists of two tube cylinders connected in parallel design.
Delivery Standard and Accessories
Delivery of NCB
including the following equipment and accessories:
3 pass vessel
coated with heat insulation of mineral wool and cladded by structured
aluminium sheet.
Accessories:
- all necessary fittings and mountings
- high pressure 3-piston plunger pump with
V-belt drive in module design
- switchboard
- burner: gas, oil or dual fuel burners with
design test of world-wide operating manufacturers.
The accessories are already mounted
and pre-wired ready for operation -
if allowed by transport sizes.
Manufacturing
Calculation of construction, selection of materials
and equipment of NCB natural circulation
boiler acc. TRD - german technical regulations
for steam boilers, after 30.05.2002 on
request also acc. PED 97/23/EC.
Manufacturing and pressure test of NCB under supervision of
TÜV Sueddeutschland,
additional calculations and acceptance of construction by foreign
supervision
organizations
like e. g. Stoomwezen, Vincotte etc. on request.
|